Product Details
Three-phase multi-function table is set telemetry, remote, remote control in one of the intelligent power distribution
instrument. It uses the international advanced instrument-specific single-chip microcomputer, through the direct
sampling of the AC signal, after processing the relevant electrical quantity, while the instrument integrates
the switch signal input and output, local display, man-machine interface and digital communication interface,
so that the The instrument can independently complete a real-time monitoring of the amount of electricity at
a outlet interval. After the use of electricity users can more effectively carry out electricity monitoring,
improve energy efficiency.
| Accuracy Measurement |
Voltage |
0.2 Class |
| Electric current |
0.2 Class |
| Active power |
0.5 Class |
| Reactive power |
0.5 Class |
| Power factor |
0.5 Class |
| Frequency |
±0.02Hz |
| Active power |
0.5S Class /0.2S Class |
| Reactive power |
1 Class /2 Class |
| Signal input |
Connection mode |
Three-phase four wire,three-phase three wire |
| Rated voltage |
AC 57.7V,AC 100V,AC 220V,AC 380V |
| Rated current |
AC 1A,AC 5A |
| Overload |
Voltage:1.2times(sustained),2times/sec (instantanenous) |
Current:1.2times(sustained),10times/5seconds (instantaneous) |
| Power waste |
Voltage:<1VA/phase,Current:<0.4VA |
| Impedance |
Voltage:>300k,Current:<20m |
| Frequency |
45-65Hz |
| Auxiliary power supply |
Working range |
AC/DC 80V-270V,AC220V |
| Power waste |
<4VA |
| Function module |
Communication interface |
1RS-485 communication,Modbus-RTU protocol |
| 1200-9600bps,the default baud rate:2400 BPS |
| Switch input |
Support 4 way dry node input |
| Switch output |
Support 3 way relay output,capacity:250V/5A AC,30V/5A DC |
| Variable output |
Supports 3 analog output:0/4-20mA or 0-5/10V |
| Electric energy pulse output |
Supports 2 way power pulse output,constant:8000imp /KWh(Kvarh) |
| Environmental |
Working temperature |
-10℃-+55℃ |
| Storage temperature |
-25℃-+70℃ |
| Relative humidity |
Less than 93%,non corrosive gas |
| Altitude |
≤2500m |
| Safety |
Insulation resistance |
>100MΩ |
| AC voltage |
AC 2KV |
Electronmagnetic compatibility |
Electrostatic discharge |
4 Class |
| Electric fast transient pulse group |
4 Class |
| Surge(impact) |
4 Class |
| Dimensions(mm) |
Box size |
120×120,80×80,96×48,96×96,72×72 |
| Hole size |
111×111,76×76,92×45,92×92,68×68 |